SmartReader Plus 6 Data Logger

 

The SmartReader Plus 6 data logger is ideal for those applications that requires monitoring of extremely high temperatures or monitoring temperature over a wide range. The datalogger has one internal channel for measuring ambient temperature and seven external channels for use with thermocouple types J, K, S, T or E.

Required with SmartReader Plus 6 Data Logger
>> TrendReader 2 Software

Required for Ethernet Connectivity 
>> TrendReader 2 Software with USB Cable Kit (#TR2-USB)
>> Read the Networking and Remote Communications Guide

NOTE: NIST Calibration is available.
Large Quantity Discounts Are Available!

SmartReader Plus 6 Logger Features

  • Monitoring Performance of Gas Fired Heating Equipment
  • Verifying Concrete Curing Temperatures
  • Process Verification
Description Part Number
SmartReader Plus 6 128KB, 8-channels: one temp, seven thermocouple inputs SRP-006-128K
SmartReader Plus 6 32KB, 8-channels: one temp, seven thermocouple inputs SRP-006
SmartReader Plus 6 1.5MB, 8-channels: one temp, seven thermocouple inputs SRP-006-1-5M
Software Kit - 1 Required
TrendReader 2 Software with RS-232 Cable (IC-101) and Manual for Smart Reader series TR2-RS232
TrendReader 2 Software with USB Interface Cable (IC-102) and Manual for Smart Reader series TR2-USB
TrendReader 2 Software CD Only (interface cable and manual not included), for SmartReader Plus, Smart Reader, IAQ and OWL Loggers TR2-Standard
Standard NIST Calibration Service
Standard NIST Temperature Calibration (1 Point) Note: 3 to 5 Day Lead Time for All Calibration Orders CAL-NIST-TEMP
Standard NIST Temp/RH Calibration (1 Point) Note: 3 to 5 Day Lead Time for All Calibration Orders CAL-NIST-RH
Optional Accessories
Fast Sampling Battery Pack BP-101
Network/Fast Sampling Power Supply - 120V - North American Version PS-201-NA
Network/Fast Sampling Power Supply - 220V - European Version PS-201-EU
Extra RS-232 Interface Cable for SmartReader, SmartReader Plus and Nautilus loggers IC-101
USB Serial Adapter CABLE-USB232

Specifications

General Specifications
Channels Eight (one internal thermistor for cold-junction compensation and seven for thermocouple inputs)
Memory Available in 32KB (21,500 readings), 128KB (87,000 readings), 1.5MB (1,048,000 readings)
Size 107 x 74 x 22 mm. (4.2” x 2.9” x 0.9”)
Weight 110 grams (3.75 ounces)
Case Material Noryl Plastic
External Connector Removable screw-type terminal strip with Common (-) connection
Operating Limits -40°C to 70°C (-40°F to 158°F) and 0 to 95% Relative Humidity (non-condensing)
Clock Accuracy ±2 seconds per day
Battery 3.6 volt Lithium, 1 Amp-Hour
Battery Life 10 year warranty (under normal use), factory replaceable
Power Consumption 5 to 10 microamps (continuous)
Sampling Methods 1. Continuous (First-in, First-out – not available with sample rates faster than 8 seconds)
2. Stop when full (Fill-then-stop)
Sampling Rates User selectable rates from 25 per second to 1 reading every 8 hrs. (BP-101 Battery Pack or PS-201 Power Supply required for sample rates faster than 8 seconds)
Resolution 12 bit (1 part in 4,096)
Mounting Magnetic backing or locking eyelet
Software Compatiblity Windows 3.1, 95, 98, 2000, ME, NT, XP, Vista (32-bit), Windows 7 (32-bit and 64-bit)
Software Requirements TrendReader 2 Software and Interface Kit
Product Approvals Meets Part 15 for Digital Devices of the Code of Federal Regulations of the Federal Communications Commission (FCC). Meets radiated and conducted emission require ments for the Interference Causing Equipment Standard for Digital Apparatus of Industry Canada (ICES-003). IEC801-2, 3, 4 and EN55011 covering ESD, RFI Immunity, EFT/Burst and Radiated Emissions respectively for the Commission of the European Communities (CE)
Resistance to X-Rays Tested for protection against a 160kV dose @ 5mA for 30 seconds (150mA-sec) @ 38 inches F.F.D. (about 100 times that of an airport x-ray machine). Tested for protection against Gamma Ray (equivalent to 0.137-1.38 mega volts) IR 192 - 28 curies @ 30 second exposure source to object distance 5”

 

Thermocouples Accepted
Type Range Resolution
J -50 to 600°C (-55 to 1100°F) 0.30°C (0.55°F)
K -100 to 1150°C (-145 to 2100°F) 0.50°C (0.90°F)
S 0 to 1450°C (32 to 2642°F) 1.0°C (1.8°F)
T -200 to 400°C (-325 to 750°F) 0.40°C (0.75°F)
E -50 to 680°C (-58 to 1250°F) 0.24°C (0.44°F)
Accuracy: ± 0.5% of range + resolution

 

Internal Temperature Sensor
Type Negative Temperature Coefficient Thermistor.
10,000 ohms @ 25°C (77°F)
Accuracy ± 0.2°C, over the range of 0 to 70°C(±0.3°F over the range of 32 to 158°F)
Range -40 to 70°C (-40 to 158°F)
Resolution 0.03°C (0.05°F) at 25°C (77°F). Better than 0.07°C(0.12°F) between -25°C (-13°F) and 70°C (158°F). Better than 0.13°C (0.23°F) between -40°C (-40°F) and -25°C (-13°F)