Sensaphone Remote Monitoring System - DATA LOGGER MALAYSIA OFFICIAL DISTRIBUTOR | DATA LOGGER MALAYSIA OFFICIAL DISTRIBUTOR

Sensaphone Remote Monitoring System

Flexible Standalone Web-Based Remote Monitoring

>> 6 Channel Inputs for External Sensors to Monitor Equipment or Environmental Conditions and Trigger Alarm or Notification with SPST Relay Dry Contact Output
>> View Live Status and History in Browser on Website
>> 8 Alarm Level Notifications Sent via Email, SMS or SNMP
>> Optional 2-Hour Battery Backup Module Available

WEB600 Remote Monitor Includes

>> Built-in Web Server with Web-Based Software
>> 120 Volt AC Power Supply

WEB600 Remote Monitor Requires

>> External Sensors

WEB600 Remote Monitor Specifications

Alarm Notifications Method: Email (SMTP), SMS (Text) and SNMP Traps
Levels: 8 Alarm Escalation Levels
Comprehensive Scheduling per Input, Profile and Alarm Destination
Temperature Range 2.8K Thermistors: -85°C to 57°C (-109°F to 115°F)
10K Thermistors: -66°C to 76°C (-87°F to 168°F)
Destinations 8 Programmable User Profiles 
4 Programmable Alarm Destinations per Profile
Communication Types Email: SMTP
Text Messages: SMS 
Web: HTTP, PDA, WAP and XML
SNMP: MIB with Traps, GET, GETNEXT and SET
MODBUS: TCP Slave Conformance Class 0 and 1
Inputs 6 Universal Inputs
Normally Closed/ Normally Open Dry Contact
2.8K/10K Thermistors
4-20mA Current Loop
Data Storage Capacity 32,000 Samples/Readings w/ Date and Time
Sampling Frequency 1 Second to 1 Month
Status Indicators Alarm Status LED
Power Status LED
Ethernet Link and Activity LEDs
Power Power Supply: Transformer 120 Volts AC 60 Hz
Consumption: 2 Watts
Protection: Metal Oxide Varistor
Backup: Optional 2 Hour Battery Backup Available (#FGD-W610)
Operating Conditions Temperature: 0°C to 50°C (32°F to 122°F)
Humidity: 0 to 95% RH, Non-Condensing
Cable Wiring Distances 24 AWG: 700 feet (Maximum)
22 AWG: 1500 feet (Maximum)
20 AWG: 2500 feet (Maximum)
Communications Ethernet 10/100 Base-T
Enclosure Indoor-Rated Plastic Housing (Wall and Desktop)
Standards Compliance  FCC Part 150B Compliant
Dimensions 5.5" x 3.25" x 1.25"
Weight 8 oz. (0.5 lbs)


Web600 Remote Monitor Web600 Remote Monitor
>> 6 Input Channels Accepting Thermistors, 4-20mA Current Loop NC/NO Dry Contacts or Universal Inputs
>> 1 Second to 1 Month Sampling Range
>> Email, SMS, SNMP Alarm Notifications
>> 120 Volt AC Powered with Optional Battery Backup
>> Built-in Web Server with Web-Based Software
Part #: FGD-W600
Standard NIST DC Voltage Calibration Service Standard NIST DC Voltage Calibration Service
>> 1 Point (per Channel) Offset Calibration
>> Traceable to NIST
>> Certificate Supplied
>> Note: 3 to 5 Day Lead Time for All Calibration Orders

Part #: CAL-NIST-DCVOLT

Standard NIST DC Voltage Calibration Service Standard NIST 4-20mA Calibration Service
>> 1 Point Offset Calibration
>> Traceable to NIST
>> Certificate Supplied
>> Note: 3 to 5 Day Lead Time for All Calibration Orders
Part #: CAL-NIST-420MA

Compatible Sensors for the Sensaphone WEB600 Remote Monitor

2.8K Temperature Sensor
>> Measure Air Temperature in Clean Indoor Environment
>> Requires Cable (#FGD-0010)
Part #: FGD-0100
2.8K Weatherproof Temperature Sensor
>> Small Sealed General Purpose Temperature Probe for Indoor/Outdoor Use
>> Accuracy: ±1°F
>> Suitable for Wet, Dry or Dirty Environments
>> Includes 12 ft Cable and Mounting Hardware
Part #: FGD-0101
10K Weatherproof Temperature Sensor
>> Small Sealed General Purpose Temp Probe
>> Indoor and Outdoor Use
>> Includes 12 Ft Cable
Part #: FGD-0102
10K Outdoor Temperature Sensor
>> Weatherproof Temperature Sensor for Outdoor Use
>> Includes 8 ft Cable
Part #: FGD-0104
10K Immersion Temperature Sensor
>> Waterproof Sensor Measures Temp of Fluids in a Pipe
>> 304 Stainless Steel Probe and a Brass WEL-B Thermowell
>> Includes 8ft Cable
Part #: FGD-0105
Humidity Sensor with 4-20mA Transmitter
>> Space Mount, Low Profile Humidity Transducer
>> Transmits Humidity Levels Back to Sensaphone Monitor
>> Requires Cable (#FGD-0010) and 24 Volt DC Power Supply (#FGD-0053)
Part #: FGD-0052
PowerOut Alert Sensor
>> Power Outage Monitoring Device to Detect Power Failures
>> Plugs into Any 110 Volt AC Outlet for Operation
>> Includes 15ft Length Cable
Part #: FGD-0054
Zone Water Detector
>> Detects Presence of Water on Floor or False Ceiling Using 10 ft WaterRope Cable
>> Up to 3 WaterRope Cables Can be Attached Together
>> Operates on 2 AA Batteries
>> Dimensions: 5.48" x 3.3" x 1.35"
>> Housing: Black Plastic >> Includes 10 ft Water Rope, Batteries, Adhesive Clamps, Metal Tapping Screws, Drywall Anchors and Rubber Feet
Part #: FGD-0056
Magnetic Reed Switch
>> Detects Entry or Intrusion
>> Used on Most Windows and Doors
>> Requires Wire (#FGD-0010) to Connect to Web600 Input
Part #: FGD-0006
Infra-Red Motion Detector
>> Detects Movement within a specific area
>> Designed to Monitor unauthorized Entry or Intrusion
>> Requires Cable (#FGD-0010)
Part #: FGD-0007
Smoke Detector w/ 120 Volt AC Power Supply
>> Photoelectric Smoke Detector Alarm
>> Powered by 120 Volt AC Connection with Alarm Output
>> Requires Cable (#FGD-0010)
Part #: FGD-0049
Smoke Detector w/ 120 Volts AC and Battery Backup
>> Photoelectric Smoke Detector Alarm
>> Powered by 120 Volt AC Connection with Alarm Output
>> Built-in Battery Backup for Power Failures
>> Requires Cable (#FGD-0010)
Part #: FGD-0049-B
22-Gauge Sensor Cable Wire
>> Length: 50 Feet
>> Shielded Wire
>> Connects Sensors to External Inputs
Part #: FGD-0010
Carbon Monoxide Detector
>> Monitor Levels from o to 300 ppm
>> LCD Display (1.0" x 0.5") Shows PPM and Menu Parameters
>> Accuracy: ±5% ppm
>> Operating Range: -20°C to 50°C (-4°F to 122°F)
>> Coverage Area: 50 ft Radius
>> Housing: Black Plastic
>> Dimensions: 7.2" x 4.9" x 1.7"
>> Compatible With Any Sensaphone That Accepts a 4-20mA Input Signal
>> Requires a 24 Volts DC Power Supply to Operate (#FGD-0053)
Part #: FGD-0065
Air Quality Sensor
>> Monitors Levels of Pollution from 0 to 100%
>> Operating Range: 0°C to 50°C (32°F to 122°F)
>> Housing: White Plastic
>> Dimensions: 2.8" x 4.7" x 1.25"
>> Compatible with Any Sensaphone with 4-20mA Input Signal
>> Requires 24 Volts DC Power Supply to Operate (#FGD-0053)
Part #: FGD-0066
Carbon Dioxide Sensor
>> Monitor Levels of Carbon Dioxide from 0 to 2000ppm
>> Compatible with Any Sensaphone with 4-20mA Input Signal
Part #: FGD-0068

Optional Accessories for the Sensaphone WEB600 Remote Monitor

Sensaphone Backup Battery Module
>> 2 Hour Battery Life for Backup to Web600
Part #: FGD-W610-B
J Type Thermocouple/4-20mA Converter
>> Converts J-Type Thermocouple to 4-20mA Input Signal
Part #: FGD-0220
24 Volt DC Power Supply
>> Required For Any Sensor Needing a 24 Volt DC Power Supply
Part #: FGD-0053
Multi-Point Wireless I/O
>> Transmitter and Receiver Accepts 2 Contacta and 1 4-20mA Signal
>> Replicates Signal Up to 5 Miles Away (Line of Sight)
Part #: FGD-0205
External Microphone w/ 25 ft Cable Extension
>> Listen-in and High Sound Alarm Capability
>> Includes 25 feet of Cable
Part #: FGD-0057
Mini Surge Protector
>> Protection from High Voltage Surges Through AC Power and Telephone Lines
>> (2) LEDs Confirm Suppressor "Protection Present" and "Grounded" Statuses
>> Voltage Compatibility: 120 Volts AC
>> Output Capacity: 15 Amps
>> Dimensions: 3.5" x 2.5" 1.75"
Part #: FGD-0067

WEB600 Remote Monitor User Manuals