SmartReader 3 Data Logger - DATA LOGGER MALAYSIA OFFICIAL DISTRIBUTOR | DATA LOGGER MALAYSIA OFFICIAL DISTRIBUTOR

SmartReader 3 Data Logger

The SmartReader 3 data logger makes easy and accurate recordings of AC current. You can use this logger with up to three external current probes for recording three-phase systems or related equipment simultaneously. The easy-to-use ACR CTs provide safe current readings by simply clamping around the power leads. 

Required with SmartReader 3 Data Logger

>> TrendReader 2 Software

Required for Ethernet Connectivity

>> TrendReader 2 Software with USB Cable Kit (#TR2-USB)

NOTE: NIST Calibration is available.

Large Quantity Discounts Are Available!

Smart Reader 3 Logger Features

  • Monitoring 3-phase current
  • Start-up or long term load analysis
  • Demand side management (DSM)
  • Monitoring mechanical systems
  • Electric motor maintenance scheduling
Description Part Number Qty 10+
SmartReader 3 Four Channel AC Current Logger SR-003 call
Software Kit - 1 Required
TrendReader 2 Software with RS-232 Cable (IC-101) and Manual for Smart Reader series TR2-RS232 call
TrendReader 2 Software with USB Interface Cable (IC-102) and Manual for Smart Reader series TR2-USB call
TrendReader 2 Software CD Only (interface cable and manual not included), for SmartReader Plus, Smart Reader, IAQ and OWL Loggers TR2-Standard call
AC Current Probes
0 to 250 Amps, 60 Hz, user-selectable (0-5, 0-25, 0-100, 0-250 Amps), AC current clamp-on probe A60FL call
0 to 250 Amps, 50 Hz, user-selectable, AC current clamp-on probe (0-5, 0-25, 0-100, 0-250 Amps) A65FL call
0 to 500 Amps, 60 Hz, user-selectable, AC current clamp-on probe (0-5, 0-25, 0-100, 0-250, 0-500 Amps) A70FL call
0 to 500 Amps, 50 Hz, user-selectable, AC current clamp-on probe (0-5, 0-25, 0-100, 0-250, 0-500 Amps) A75FL call
Standard NIST Calibration Service
Standard NIST Temperature Calibration (1 Point) Note: 3 to 5 Day Lead Time for All Calibration Orders CAL-NIST-TEMP call
Optional Accessories
USB Serial Adapter CABLE-USB232 call
ACR RS-232 Serial Interface Cable (Limited Quantity - 2 Available) LIC-101--U-- call
ACR RS-232 Serial Interface Cable LIC-101 call

Smart Reader 3 Logger Specifications

General Specifications
Channels Four:
- Three for AC current for use with ACR Current probes
- One internal for ambient temperature
Memory 32 KB (32,767 readings)
Size 107 x 74 x 22 mm. (4.2” x 2.9” x 0.9”)
Weight 110 grams (3.75 ounces)
Case Material Noryl Plastic
External Connector Removable screw-type terminal strip with Common (-) connection
Mounting Magnetic backing or locking eyelet
Operating Limits -40°C to 70°C (-40°F to 158°F) and 0 to 95%
Relative Humidity (non-condensing)
Clock Accuracy ±2 seconds per day
Battery 3.6 volt Lithium, 1 Amp-Hour
Battery Life 10 year warranty (under normal use), factory replaceable
Power Consumption 5 to 10 microamps (continuous)
Sampling Methods 1. Continuous (First-in, First-out)
2. Stop when full (Fill-then-stop)
Sampling Rates User selectable rates from 8 seconds to once every 5 days
Resolution 8 bit (1 part in 256)
Software Compatiblity Windows 3.1, 95, 98, 2000, ME, NT, XP, Vista (32-bit), Windows 7 (32-bit and 64-bit)
Software Requirements TrendReader 2 software and interface cable
Certifications and Standards

- Certified to CE standard EN50082-1: 1992 (European Generic Immunity) covering ESD, RFI and EFT/B
-Meets CE standards EN55011 Class B: 1991 (European Radiated Emissions) and CISPR Class B: 1991(International Radiated Emissions)

Resistance to X-Rays - Tested for protection against a 160kV dose @ 5mA for 30
seconds (150mA-sec) @ 38 inches F.F.D. (about 100 times that of an airport x-ray machine)
- Tested for protection against Gamma Ray (equivalent to 0.137-1.38 mega volts) IR 192 - 28 curies @ 30 second exposure source to object distance 5”
Logger Accuracy ± 4% of full scale above 10% of range

 

Internal Temperature Sensor
Type Negative Temperature Coefficient Thermistor.
10,000 ohms @ 25°C (77°F)
Accuracy ± 0.2°C, over the range of 0 to 70°C (±0.3°F over the range of 32 to 158°F)
Range -40 to 70°C (-40 to 158°F)
Resolution 0.4°C (0.7°F) at 25°C (77°F); better than 1 °C (1.8°F) between -25°C and 70°C (-13°F and 158°F); better than 2.0°C (3.6°F) between -40°C and -25°C (-40°F and -13°F)

 

Current Probes

Part Number

Range

A60FL (60 Hz)

5, 25, 100, 250 Amps

A65FL (50 Hz)

5, 25, 100, 250 Amps

A70FL (60 Hz)

10, 50, 250, 500 Amps

A75FL (50 Hz)

10, 50, 250, 500 Amps

Current Channels Accuracy: ±3.5% of full scale (above the lowest 10% of range)