Power & Harmonics Analyzer - DATA LOGGER MALAYSIA OFFICIAL DISTRIBUTOR | DATA LOGGER MALAYSIA OFFICIAL DISTRIBUTOR

Power & Harmonics Analyzer

Complete with (3) 1000A Current Clamps, 4 Voltage Leads with alligator clips, 8 AA Batteries, AC Adaptor, Software, PC interface Cable and Carrying Case

The Power & Harmonics Analyzer provides accurate display of mulitple measurements and transient events including current, voltage, total harmonic distortion and many other power quality measurements. The power analyzer includes software, batteries,cable, voltage leads, current clamps and carrying case.

Included with each Power & Harmonics Analyzer

>> (3) 1000 Amp Current Clamps
>> 4 Voltage Leads with Alligator Clips
>> 8 AA Batteries
>> AC Adapter
>> Windows PC Software
>> PC Interface Cable
>> Carrying Case

NOTE: Large Quantity Discounts Are Available!

Harmonics Analyzer Features

  • Large Backlit LCD Displays up to 35 parameters in one screen
  • True RMS power measurements with Harmonics display ( 1-99th order)
  • Simultaneous Harmonics and Waveform display
  • Display of Total Harmonic Distortion
  • Dislplays Active Power (kW), Apparent Power (kVA), Reactive Power (kVAR) and Power Factor
  • kWH and KVARh energy measurements
  • Maximum Demand with programmable period
  • Current measurements to 1000A with adjustable CT ratio
  • Voltage measurements to 600V with adjustable VT ratio
  • Graphical Phase diagram with system parameters
  • 3-phase Voltage or Current Unbalanced Ratio
  • 3-phase Voltage or Current Unbalanced Factor
  • Calculated Unbalanced Current through Neutral Line
  • Datalogger records up to 52428 records in single phase (17476 records in 3-phase)
  • Optically isolated RS-232 interface with software to download Waveforms, Power Parameters and Harmonics

Harmonics Analyzer Specifications

Functions Range Basic Accuracy
ACV (true rms) 600 Volts ±(0.5%rdg + 5d)
ACA 1000 Amps ±(0.5%rdg + 5d)
Active Power (kW) 9.999 MW ±(1%rdg + 8d)
Apparent Power (kVA) 9999 kVA VA=Vrms x Arms
Reactive Power (kVAR) 9999 kVAR VAR=sqr(VA2 - W2)
Power Factor 0.0 to +1.00 ±(1.5%°rdg ±8d)
Frequency 45-65Hz 0.1Hz
Phase -180.0°~ 0°~+180.0° ±1°
Harmonics 1 to 99 ±2%
Crest Factor 1.00 to 99.99 ±(5% + 30d)
Peak AC Voltage accuracy   ±(5%rdg + 30d)
Peak AC Current accuracy   ±(5%rdg + 30d)
Active Power Energy (kWh) 0mWh to 999,999kWh
Reactive Power Energy (kVARh) 0.0kVARh to 1000MWh
Datalogging 52,428 records (1 Phase)/17,476 records (3 Phase)
Warranty/CE 1 year / CE Approved
Dimensions 10.1" x 6.1" x 2.3" (257mm x 155mm x 57mm)
Weight Meter: 2.5 lbs (1160g) Clamp: 1.3 lbs (600g)