>> 3 Channel Meter Supports Full Range of Splilt-Core or RoCoil Rogowski-Style CTs (Sold Separately)
>> Outputs to a RS-422/485 Serial Communication Supporting BACnet, Modbus or Pulse Only Modes
>> Patented PhaseChek™ LED Indicators Guarantee Correct CT Orientation
>> US and Int'l Versions Available w/ Colored Voltage Leads
>> Requires Powerscout Communications Package (#PS-COMPAK-USB) & Current Transformers (CTs)
The PowerScout 3+ Power Meter can measure over 50 energy and power parameters. This single-point 3-phase power meter features PhaseChek™ circuitry, LED indicators, line-powered 60 to 600 volt Phase-Phase power supply and RS-422/485 serial connection. The Dent PowerScout 3+ supports BACnet and Modbus Industry-Standard Protocols. In addition, the power meter has a "Pulse Output Mode" and when connected to a pulse data logger will log pulses based on accumulated values(s) such as system kWh, kVARh and kVAh. A single BACnet client can support up to 127 Powerscout 3+ and a Modbus Control System can support up to 254 meters.
Specifications for PowerScout Power Meter
Service Types | Single Phase Three Phase-4 Wire (Wye) Three Phase-Three Wire (Delta) |
Outputs | Pulse BACnet (Master Slave Token Passing Protocol) Modbus |
Voltage | Channels: 3 Line-to-Neutral: 80 to 346 Volts AC Line-to-Line: 600 Volts Safety Rating: CAT III |
Current | Channels: 3 Measurement Range: 0 to 5,000+ Amps Note: Range is Dependant upon Current Transducer |
Max Current Input | 175% of Current Transducer Rating |
Measurement Type | True RMS using High Speed Digital Signal Processing (DSP) |
Line Frequency | 50/60/400 Hz |
Waveform Sampling | 12 kHz |
Parameter Update | 500 milliseconds |
Measurements | Volts, Amps, kW, kWh, kVAR, kVARh, Apparent Power Factor (aPF), Displacement Power Factor (dPF). All Parameters for Each Phase and for System Total |
Accuracy | Better than 1% (<0.5% Typical) for V, A, kW,kVAR, kVA, PF |
Resolution | 0.01 Amp. 0.1 Volt, 0.01 Watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor |
LEDs | Bi-Color LEDs (red and Green) 1 LED to Indicate Communication 3 LEDs for Correct phasing (PhaseChek - Green: Voltage & Current on Smae Phase - Red: incorrectly Wired) 2 Digital Channel Indicators |
Pulse Output | Open Collector Max Current: 75 mA Open Voltage: 40 Volt Max NOTE: The pulse output is scaled by the same data scalar register (44062) as are the Modbus registers. For Example, When the data scalar is set to 3, each pulse will represent 0.1 kWh, 0.1 kVAh and 0.1 kVARh |
Communications | Output: Pulse, Modbus or BACnet over RS-485 Distance: 1200 Meters @100K bits/second Data Range (Max) Baud Rate: 9600 (Modbus Default), 19200, 38400, 57600, 76800 (BACnet Default), 115200 Data Bits: 8 Parity: None, Even and Odd Stop Bit: 2, 1 and 0 Data Formats: Modbus Protocol OR BACnet (MS/TP) Protocol Power: From L1 Phase to L2 Phase. 80 to 600 Volts AC CAT III 50/60Hz 70 mA Max. Non-User Replaceable 0.5 Amp Internal Fuse Protection |
Operating Range | Temperature: -7C to 60C (-20F to 140F) Humidity: 5% to 95% RH |
Enclosure | ABS Plastic, 94-V0 Flammability Rating |
Software Compatibility | Windows 7 (32 or 64 Bit), Vista (32 or 64 Bit) and XP |
Weight | 357 grams (12.6 oz.) - Excluding CTs |
Dimensions | 21.8cm x 5.8cm x 4.0cm (8.6" x 5.8"x 1.6") |
Part # | PS3P-US |
Base Price | (CTs Sold Separately) |
Transformer & Voltage Lead Colors |
Powerscout Communications Package >> Compatible with Powerscout 3+ and Powerscout 18
>> Includes Viewpoint Software, USB-RS485 Adapter Assembly and User Manual |
Part #: PS-COMPAK-USB |